See the boiler room without going downstairs
Live boiler and pump status, temperatures and alarms for every building you manage, in any browser.
Already a client? Client sign in
Buildings
3
Sample building A
Brooklyn walk-up
Online · 0 alarms
Supply 178.4°
Sample building B
Queens co-op
Online · 1 alarm
Supply 171.2°
Sample building C
Bronx
Offline 6 min
Supply --.-°
The boiler room, on one screen
Each building gets a page like this. You and our engineers open the same one.
Buildings 3
- Sample building A
- Sample building B
- Sample building C
Sample building A
Brooklyn walk-up · 2 boilers
- Supply
- 178.4°
- Return
- 158.9°
- Outdoor
- 41°
- Hot water
- 124°
- Boiler 1Running
- Boiler 2Off
- Pump 1Running
- Pump 2Off
High supply temperature · Boiler 1
Started 06:12 · Cleared 06:41
Acknowledged 06:20 by the superPump 1 failed to start
Started 21:40 · Cleared 22:15
Acknowledged 21:52 by our engineer
6 hDayWeek
Online, and when it last reported.
Five minutes of silence marks it offline, with an alarm.
Supply, return, outdoor and hot water.
Which boilers and pumps are running, off or in fault.
Alarms: when they started, who acknowledged them, when they cleared.
Trends over 6 hours, a day or a week.
So a question about last Tuesday night has an answer.
Every building you manage on one list.
How a reading gets from cellar to phone
The controls never need the cloud to run the building. The cloud only listens.
178.4°F
One reading from the sample building, as each layer sees it. Illustrative values.
A sensor in the supply pipe
An immersion sensor in the pipe leaving the boiler.
TT-101 · supply main · 178.4°F
The controller reads it
The controller reads it on an analog input and runs the plant on it. If the internet drops, the building still heats.
P2-550 · analog input 3 · 178.4°F
It leaves through a door that only opens outward
Encrypted, over a cellular gateway or the building's ethernet. Each panel has its own login and can write only its own topic.
nio/plc-0142/status {"temps":{"supply_f":178.4}} MQTT · TLS · port 8883
Our servers keep it
The broker takes it, our ingest service checks it and the database stores it against your building.
readings · plc-0142 · supply_f 178.4 · 2026-10-13 18:00:00
It's on your screen
The building card updates on its own in any browser. Setpoints change only at the touchscreen in the cellar.
Supply 178.4° · Boiler 1 running · updated just now
2:14 a.m., low water
A boiler that trips at 2 a.m. used to mean a cold building by breakfast. Here's the same cellar, one event at a time.
· B1 LWCO
Low-water cutoff trips on boiler 1
The burner's own safety shuts the flame. The controller sees the contact open.· PLC-0142
The controller sends it out at once
It doesn't wait for the next snapshot.nio/plc-0142/status "alarms":[{"code":"LOW_WATER", "severity":"critical"}]· PORTAL
It's on the portal
The building card turns red for everyone who watches this building, with the time it started.· B2
Boiler 2 takes the lead
The controller keeps boiler 1 locked out and fires boiler 2. Supply dips to 151°F and is back over 170°F by 02:40.· ACK
Acknowledged in the morning
Boiler 2 carried the building through the night. The super takes the alarm on the portal, which records who took it and when.· CLEAR
Cleared
Water feed checked, boiler 1 reset. The alarm, the acknowledgement and the trend around it stay in the building's history.
Text and email alerts are next on our list. Until they ship, the portal keeps the record. Silence counts as a fault: five minutes without a report and the building is marked offline, with an alarm.
Illustrative sequence. Times are an example.
Sample building A
Brooklyn walk-up
Critical
Low water cutoff · Boiler 1 · Started 02:14:07 · Not acknowledged
- Supply
- 178.4°
- Return
- 158.9°
- Outdoor
- 41°
- Boiler 1Tripped
- Boiler 2Off
- Pump 1Running
Supply, last 6 hours
Sample building. Not live data.
Who sees which building
| Role | Sees | Example |
|---|---|---|
| Management company | Every building in its portfolio | A property manager sees all of the company's buildings on one list, each with its status and active alarms. |
| Super or building staff | Only their building | The super at one address sees that boiler room and its live alarms from a phone, and no other building. |
| Nio Controls | Everything, for support | Our engineers can pull up any monitored building while you're on the phone with us. |
Monitoring plans. Each building on a plan gets its own page on the portal: live readings, alarms and the history behind them.
What's in the cellar, and how it's secured
A boiler room on the internet should be boring.
The boiler room only connects out.
Hardware
- Controller
- AutomationDirect Productivity 2000, P2-550 CPU, I/O sized with spare points
- Sensors
- Immersion sensors on supply and return, an outdoor sensor out of the sun, a hot-water tank sensor, run and fault contacts
- Link
- A cellular gateway, or a port on the building's ethernet
- Touchscreen
- On the panel door. Setpoints change here.
Connection
- Direction
- Outbound only. Nothing on the internet can open a connection into the cellar.
- Encryption
- TLS from the controller, or a VPN over cellular where a controller can't do TLS
- Identity
- Each controller has its own broker login and can write only its own topic
- Access
- Who sees which building is enforced in the database
- Portal
- Read-only by default. Alarms can be acknowledged; setpoints can't be changed.
- Silence
- Five minutes without a message means offline and an alarm. A controller that loses power says so on the way out.
Questions boards and managers ask
Something else? Call (347) 369-7269.
Does this replace my burner control?
No. The controller sits alongside the burner management and the boiler's own safeties. It reads status and runs setpoints and sequencing, and the burner's safeties stay in charge of the flame. We work alongside your boiler service company too: we look after the controls, the sensors and the panel, and they keep the burner, the boiler and the fuel. When the burner itself fails, they're the call, and the portal shows them what happened.
What happens if the internet goes down?
The controller keeps running the building on its own. After five minutes without a message (the default, set per building), the portal marks the building offline and raises an alarm for everyone who watches it. When the connection comes back, the live view picks up again.
Do we need building internet?
Not necessarily. We can use the building's ethernet if it reaches the cellar, or put in a cellular gateway so monitoring doesn't depend on the building's network at all.
Who can change setpoints from the portal?
Nobody, by default. The portal shows status and lets the people you name acknowledge alarms. Setpoints change at the touchscreen in the cellar. If a building wants remote adjustments, that's a separate conversation with its own safeguards.
Can you monitor controls we already have?
Often, yes. If the existing controller speaks Modbus or has dry contacts, we add a controller that reads it and reports to the portal. BACnet usually goes through a gateway; we confirm it on the site visit.
How far back does the history go?
Every reading is stored, and charts show five-minute averages. Alarms stay in the building's history.